ET 200MP Distributed I/O System
System Manual, 01/2013, A5E03723484-01
31
Application planning
4
4.1
Hardware configuration
Maximum configuration
●
The integrated power supply of the interface module feeds 14 W into the backplane bus.
Up to 12 I/O modules can be supplied this way. The exact number of operable modules is
the result of the power budget (see chapter Power budget calculation (Page 32)).
●
A maximum of one power supply module (PS) upstream from the interface module and
two downstream from the interface module is possible.
●
If you use a power supply module (PS) upstream from the interface module, the
maximum possible configuration is a total of 32 modules (up to 30 modules downstream
from the interface module).
0D[LPXPPRGXOHVLQWRWDO
36
,0
0RGXOHV
Figure 4-1
Maximum ET 200MP configuration
Rules: Arrangement of the modules
The following table shows the slot number assignment:
Table 4- 1
Assignment of slot numbers
Slot
Modules
Note
0
Power supply module (optional)
Before the interface module
1
Interface module
-
2 - 31
I/O modules /
max. 2 power supply modules, depending
on the configuration
After the interface module
See also
Summary of Contents for simatic ET 200MP