Wiring
6.4 Wiring rules
ET 200MP Distributed I/O System
System Manual, 01/2013, A5E03723484-01
57
6.4
Wiring rules
Wiring rules
Table 6- 2
Wiring rules
Wiring rules for...
Interface module
40-pin front connector
(screw-type connection)
Power supply module
-
up to 0.25 mm
2
-
Connectible conductor cross-sections for
solid wires
-
AWG
*:
up to 24
-
0.25 to 2.5 mm
2
0.25 to 1.5 mm
2
1.5 mm
2
Without wire end
ferrule
AWG
*
: 24 to 16
AWG
*
: 24 to 16
AWG
*
: 16
0.25 to 2.5 mm
2
0.25 to 1.5 mm
2
1.5 mm
2
Connectible
conductor cross-
sections for stranded
wires
With wire end
ferrule
AWG
*
: 24 to 16
AWG
*
: 24 to 16
AWG
*
: 16
Number of wires per connection
1
1 or combination of 2
wires up to 1.5 mm
2
(total) in the same wire
end ferrule
1
Length of stripped wires
10 to 11 mm
10 to 11 mm
7 to 8 mm
Without plastic
sleeve
Design A, 10 mm long
Design A, 10 mm and
12 mm long
Design A, 7 mm long
End sleeves
according to
DIN 46228
With plastic sleeve
0.25 to 1.5 mm
2
Design E, 10 mm long
Design E, 10 mm and
12 mm long
Design A, 7 mm long
Sheath diameter
-
-
8.5 mm
Tool
3 to 3.5 mm Phillips
screwdriver, conic
design
3 to 3.5 mm Phillips
screwdriver, conic design
3 to 3.5 mm Phillips
screwdriver, conic
design
Tightening torque
-
from 0.4 Nm to 0.7 Nm
from 0.5 Nm to 0.6 Nm
* AWG: American Wire Gauge
Summary of Contents for simatic ET 200MP
Page 4: ...Preface ET 200MP Distributed I O System 4 System Manual 01 2013 A5E03723484 01 ...
Page 8: ...Table of contents ET 200MP Distributed I O System 8 System Manual 01 2013 A5E03723484 01 ...
Page 118: ...Service Support ET 200MP Distributed I O System 118 System Manual 01 2013 A5E03723484 01 ...
Page 126: ...Index ET 200MP Distributed I O System 126 System Manual 01 2013 A5E03723484 01 ...