Technology subrack
7-12
Hardware - SIMADYN D
Edition 03.2001
Analog input 2
10 98
Ground, analog inputs and outputs
11
99
All grounds are connected mutually via inductivity and with electronics
ground.
The grounds connections of
interfaces 1 and 2
analog inputs/outputs
binary inputs/outputs.
incremental encoders 1 and 2
are connected to the T400 electronics ground through 0 Ohm resistors,
reactors and capacitors which can be soldered-out. For production-related
reasons, the 0 Ohm resistor is an SMD device (not separately connected)
and when required must be soldered-out (to interrupt the electrical
connection)!
7.2.9 Technical data
No. of slots occupied
1
Dimensions W x H x D [mm]
20.14 x 233.4 x 220
Weight
approx. 0.6 kg
The T400 requires the following voltages at the upper backplane bus
connector X1:
Rated voltage
min. max.
Typ. current drain
+5 V
+4.75 V
+5.25 V 1000 mA
+15 V
+14.4 V
+15.6 V 140 mA + encoder load
(max. 100 mA, electronically limited)
-15 V
-15.6 V
-14.4 V
140 mA
24 V (external)
20 V
30 V
150 mA + binary output current
Note:
Grounding
General data
Power supply