Input/output modules
5-50
Hardware - SIMADYN D
Edition 12.2004
5.5.3 Connector assignment X6
Connector X6 (20-pin plug connector) connects the signals for:
•
4 binary inputs
•
4 binary outputs
•
1 speed input
The
SU11
interface module can be connected via the
SC12
plug-in cable
(1:1 connection from the module to the terminals):
ITDC
X6 Pin
Designation SU
11
X2
Connector
designation
for
configuring
1
Binary input 1
1 X6A
2 Binary
input 2
2
3 Binary
input 3
3
4 Binary
input 4
4
5
Binary output 1
5
X6G
6
Binary output 2
6
7
Binary output 3
7
8
Binary output 4
8
9 P
ext
, positive power supply, max. 30 V
9
10 M
ext
, 0V power supply
10
11
Speed sensing, track 1A-
11
X6C
12
Speed sensing, track 1A+
12
13
Speed sensing, track 1B-
13
14
Speed sensing, track 1B+
14
15
Speed sensing, zero pulse 1N-
15
16
Speed sensing, zero pulse 1N+
16
17 Coarse
pulse
17
18 GND
ext.
18
19 GND
ext.
19
20 n.
c.
20
Table 5-41 Pin assignment ITDC, connector X6 and terminal assignment SU11
5.5.4 Connector assignment X7
Connector X7 (sub-D 50-pin) connects the signals to control (gate) a SITOR
set (three-phase bridge).
Via plug-in cable:
•
SC17.2
(screened round cable, 50-pin SUB-D, 2m long),
or
•
SC31.2
(screened round cable, 50-pin SUB-D, 10m long)
The module can be directly connected to a SITOR set.
SU11 binary
input/output and
speed sensing via
cable SC12
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182