Input/output modules
5-4
Hardware - SIMADYN D
Edition 12.2004
5.1.2 Connector assignment X5
EA12
X5
Significance Associated
test socket
SU11
Connector
designation when
configuring
1
Analog output 1
X11 SIG
1
X5A
2
Ground
X11 COM
2
3
Analog output 2
X12 SIG
3
X5B
4
Ground
X12 COM
4
5
Analog output 3
X13 SIG
5
X5C
6
Ground
X13 COM
6
7
Analog output 4
X14 SIG
7
X5D
8
Ground
X14 COM
8
9
Analog output 5
X15 SIG
9
X5E
10
Ground
X15 COM
10
11
Analog output 6
X16 SIG
11
X5F
12
Ground
X16 COM
12
13
Analog output 7
X17 SIG
13
X5G
14
Ground
X17 COM
14
15
Analog output 8
X18 SIG
15
X5H
16
Ground
X18 COM
16
17 Electronics
ground
(connected with the
electronics ground via 0
Ohm resistor)
--- 17
18 Electronics
ground
(connected with the
electronics ground via 0
Ohm resistor)
--- 18
19 Ground
---
19
20 Ground
---
20
Table 5-3 EA12 connector- and SU11 terminal assignment
All of the
"ground" terminals
are connected together via 0 Ohm resistors
and are connected to electronics ground via an associated inductance.
5.1.3 Application information and noise immunity
•
operation
without fan
is possible
•
noise-immune operation is only possible if the module is tightly screwed
into the subrack
The input/output signals must be screened on the plant/system side. The
screen must be connected through the largest possible surface area to the
screen rail between the interface module and where the cable enters or exits
the cabinet.
SU11 terminal
assignment
Screening