CPU module
Hardware - SIMADYN D
3-15
Edition 03.2001
3
3.2.1 Supplementary components
•
MS5 and MS51 program memory modules
•
Cable SC57 for PC connection, 9-core, 5 m
•
Cable SC7 to connect an interface module, 10-core, 2 m
If additional input/output signals and other functions are required, then these
can be implemented by inserting a maximum of 2
expansion modules
:
•
IT41
•
IT42
•
ITDC
•
ITSL
3.2.2 Application information and noise immunity
•
Operation
without fan
is not possible
•
Noise-immune operation is only possible if the module is tightly screwed
into the subrack
•
Do not insert or withdraw the module when the subrack is powered-up
For more information regarding EMC and ambient conditions, refer to the
section "General technical data“!
3.2.3 Technical data
Number of slots occupied
1
Dimensions W x H x D [mm]
20.14 x 233.4 x 220
Weight
approx. 0.51 kg
Rated voltage
min. max.
Typical current drain
+5 V
+4.75 V
+5.25 V 1700 mA
+15 V
+14.4 V
+15.6 V 50 mA
-15 V
-15.6 V
-14.4 V
30 mA
24 V (external)
20 V
30 V
100 mA + binary output currents
Other information
General data
Power supply
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182