General technical data
1-6
Hardware - SIMADYN D
Edition 08.2005
1.1.4.2 Professionally-trained and knowledgeable personnel
Only professionally-trained, knowledgeable personnel may configure,
install, commission and operate SIMADYN D.
1.1.4.3 CE
Mark
SIMADYN D components have
no
CE Mark for the following reasons:
•
they cannot be practically used autonomously
•
they are not generally available
•
they can only be used by specially-trained personnel
NOTE
If a CE Mark is required, this is the responsibility of the manufacturer of
the machine/complete system.
1.1.4.4 Connecting external voltages
If external voltages (e. g. pulse encoders) are connected to SIMADYN D
inputs, which are supplied from an external power supply, then this
external supply must also be shutdown when the SIMADYN D power
supply is shutdown or fails.
1.1.5 Mounting
SIMADYN D components must be mounted in a metal cabinet, enclosed
on all sides.
1.1.6 Cables
All signal cables which are connected to SIMADYN D must be screened.
1.1.7 Potential
bonding
In order to ensure disturbance-free operation, the components which are
connected and communicate with one another may not be at different
potentials. This means that all components must be connected with one
another through potential bonding cables.