Subracks
Hardware - SIMADYN D
2-7
Edition 04.2011
2
The subrack must be able to discharge hot air:
The discharged air may not be restricted by mounted components
When mounting equipment or other components, a minimum clearance
of 60 mm must be maintained above and below the subrack
If the subrack is mounted in a cabinet, the cabinet must have air ventilation
slots. If the cabinet is enclosed, the subrack must be force-ventilated (an
SR6V must be used).
If two subracks are mounted one on top of the other, there must be a
minimum 120 mm clearance between the two subracks, whereby the upper
subrack must be separated from the lower subrack by an air deflection plate.
2.1.6 Mounting
guidelines and noise immunity
The subrack must be connected to the grounding rail via the connecting
studs through a min. 6 mm² cable which should be kept as short as
possible.
Potential bonding using the PE pin of line connector X1 is not sufficient!
All of the cabinets associated with networked SIMADYN D drives must be
connected with one another through a potential bonding conductor
having a minimum cross-section of 16 mm².
Empty slots must be provided with SIMADYN D slot covers (SR81, SR82,
SR83).
All modules must be tightly screwed into the subrack.
No undamped contactors may be used in a cabinet together with
SIMADYN D.
If undamped contactors are mounted in a cabinet next to SIMADYN D,
the cabinets must have a metal partition between them.
The protective contactor is connected at the subrack and at the power
supply. Both components must be at protective conductor potential.
Before removing the power supply, the connecting cables must be
disconnected. The connecting cables must first be disconnected from the
supply so that they are in a no-voltage condition!
The screens of screened cables must be directly connected to the
grounding- or screen rails and fed to the interface modules, still
screened.
NOTE
Additional information regarding EMC and the ambient conditions, refer
to the Section „General technical data“!
Discharged air