Subracks
Hardware - SIMADYN D
2-29
Edition 04.2011
2
The screens of screen cables must be directly connected to the
grounding- or screen rails and fed to the interface modules, still
screened.
NOTE
Additional information regarding EMC and the ambient conditions, refer
to Section „General technical data“!
2.3.7 Technical
data
AC power supply according to DIN IEC 38
Supply voltages
(can be set using the voltage selector switch)
AC 115 V
AC 230 V
Input voltage range
±10%
±10%
Input frequency
47-63 Hz
47-63 Hz
Input current
0.8 A
0.4 A
Non-periodic overvoltages
acc. to DIN VDE160, A5.3.1.1.2
Voltage 460
V
Duration 1.3
ms
Recovery time, min
0.1 s
Events per hour
max. 10
Brief voltage dips
acc. to DIN VDE 0160, A5.3.1.1.3
Voltage 0
V
Duration 5
ms
Recovery time, min
0.1 s
Events per hour
max. 10
Output voltage 5 V
+5.1 V +/- 0.1 V
Output current
3 A
Ripple
< 50 mVss
Commutating spikes
< 5% (of 5V)
Overvoltage protection
With suppressor diode,
to protect the modules
Stabilization time
< 80 ms after Uin= 230 V;
<1 ms
after a load step (0.5 ->1)*Irated
Output v15 V
+15 V +/- 0.3 V
Output current
0 to
0.5 A
Ripple
< 150 mVss
Input voltages
Output voltages
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182