Program memory modules / Interface modules
Hardware - SIMADYN D
8-9
Edition 04.2011
8
8.3.2 Technical data
Mounting system
Can be snapped onto mounting rails
Dimensions (W x H x D)
135 x 77 x 59
Weight 0.2
kg
External power supply
+24 V DC
Range
+20 to +30 V DC
Briefly (t<500 ms)
1,5 x V
rated
Current drain at 24 V
170 mA at the rated output current
Signal level
input
+/- 10 V
output
+/- 10 V
Input resistance
100 k
Ω
Signal level
+10 V
Output load resistor
>1 kOhm
Zero point error
1)
+ 2 mV
Maximum error
+10 mV
Push-pull output
5 mA
Transfer frequency range:
0 to 1 kHz
⏐
A/AO
⏐
= 0 dB
1 to 3 kHz
⏐
A/AO
⏐
ε
3 dB
1)
25
°
C ambient temperature
8.3.3 Connector assignment
Terminal block -X2
Terminal block -X3
Terminal Designation Terminal Designation
031
Pos.
input signal
04
Output signal
032
Neg.
input signal
05
Output ground
05
Input ground
L+
P24 power supply P
ext
1S
Push-pull output
1S
Connected with terminal
X2/3S
2S
Terminal connected with
X2/05 input ground
2S
Connected with terminal
X3/05
3S
Connected with X3/1S
M
M24 power supply M
ext
Table 8-3
Connections of terminal blocks X2 and X3
General data
Power supply
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182