Connection
6-3
©
Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
A SICLOCK GPSDEC decoder is connected as shown in Figure 6-5.
Figure 6-5 Connection of the radio clock SICLOCK GPSDEC to RADIO CLOCK 1
Functional check
The "RADIO CLOCK" LED on the front panel must flash at about 1Hz when the
GPSDEC is received correctly.
The parameter /Inputs/Input 1/Status (0.20.02) must change to "GPS" or "DCF77"
after about three minutes reception.
Caution
A SICLOCK GPSDEC may only be operated as an active radio clock.
Operation as a passive radio clock leads to the destruction of the
SICLOCK GPSDEC.
Table 6-2
Recommended assignment of parameters to the GPSDEC decoder for
synchronizing a SICLOCK TC100
Parameter
Setting
Time difference from GMT
00:00
Daylight saving time change
„none“
X1.5-8 (DCF77TTY)
„DCF without ZZB“
;
PD[P
'&)77<
5$',2&/2&.%
5$',2&/2&.$
5$',2&/2&.*1'
6.3.3
SICLOCK GPSDEC
(SICLOCK GPSDEC has been discontinued, please use SICLOCK GPS1000)
Summary of Contents for SICLOCK TC100
Page 1: ...SICLOCK s SICLOCK TC100 Plant Central Clock Operating Instructions 11 2012 ...
Page 5: ...Preface Preface 4 Siemens AG 2010 All Rights Reserved SICLOCK TC100 Operating Instructions ...
Page 33: ...Mounting 5 3 Siemens AG 2010 All Rights Reserved SICLOCK TC100 Operating Instructions ...
Page 43: ...Connection 6 4 Siemens AG 2010 All Rights Reserved SICLOCK TC100 Operating Instructions ...
Page 101: ...Technical data 13 Siemens AG 2010 All Rights Reserved SICLOCK TC100 Operating Instructions ...
Page 113: ...ESD guidelines B 11 Siemens AG 2010 All Rights Reserved SICLOCK TC100 Operating Instructions ...
Page 121: ...Glossary D 1 Siemens AG 2010 All Rights Reserved SICLOCK TC100 Operating Instructions ...
Page 124: ...Siemens AG Industry Sector Postfach 48 48 90026 NUREMBERG GERMANY www siemens com siclock ...