3-17
Operation
TO TEST SYSTEM, LOOP & DEVICE
Use this function to test the System, its
loops, and its devices, including ground
fault, battery voltage and current, and the
LEDs.
To return to the Main Menu display, press
HELP again:
ACKNOWLEDGE LIST CONTROL TEST
We discuss the Test menu in detail begin-
ning on page 3-42.
Entering Your Password
If you select CONTROL, TEST, or WALK-
TEST, the System asks for your password:
ENTER YOUR PASSWORD:
If you press HELP, the System explains
this function; press HELP again to return to
the previous display.
Type your (1-5 digit) password, using the
numeric keypad. The System shows an
asterisk for each digit that you type. (Use
the Left arrow key to erase an error.)
When you have typed the entire password,
press ENTER. If your password does not
match a password stored in the System,
the System briefly displays the following
message and then returns you to the first
password display:
ACCESS DENIED
If your password level is not high enough to
use the Test functions, the System briefly
displays the following message and then
returns you to the first password display:
PASSWORD LEVEL NOT HIGH ENOUGH
PASSWORD LEVELS
Rev 5.0 and Above
Highest
Test
Z
Control
Lowest
Walktest
Below Rev 5.0
Highest
Walktest
Y
Test
Lowest
Control
The System gives you three chances to
enter an acceptable password before it
returns you to the Main Menu.
If the System accepts your password, it
displays the Control, Test, or Walktest
menu. We discuss those menus later in this
section.
Entering a Module Number and Device
Number
The System asks you to supply a module
number or device number, or both, during
certain functions described in the pages
that follow. Below is a summary of the
procedures involved.
NOTE:
The terms module number and
module address are used inter-
changeably in this manual.
Entering a Module Number
The System displays
TYPE IN MODULE NUMBER:
If you press HELP at this point, the System
displays the following explanation:
3 DIGIT MODULE NO., PRESS <ENTER>
Press HELP again to return to the previous
display. Type all three digits, including
leading zeros, and press ENTER.
When you type the module number, use
the Left arrow key as a backspace key to
erase errors.
Entering a Device Number with the
Module Number
The System displays
TYPE IN THE DEVICE NUMBER:
(If you press HELP at this point, the System
displays the following explanation:
3 DIGIT MODULE 3 DIGIT DEVICE
Press HELP again to return to the previous
display. Type all of the digits, including
leading zeros, and press ENTER.)
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...