J-6
Appendix J
Trouble Message
The Probable Cause Is:
Node Not Responding
XNET wiring and/or NIM-1W module is
defective.
Out of RAM Call Support
The configuration upload is too large.
Out of Tasks Call Support
Contact the Siemens Industry, Inc. Techni-
cal Services Department.
Output Disarmed
Indicates that an output point has been
manually disarmed.
PRE 1 Level
AnaLASER device has reached its
pre-alarm setting.
Pre-alarm
Device has reached its pre-alarm setting.
Pre-dirty Analog Volt. Reached
IEC compensation has reached a level
where the detector should be cleaned.
Printer Off Line/Fault
A supervised printer is not responding.
Printer Out Of Paper
The printer has run out of paper.
Relay Coil Open
The relay coil at this address is open.
Relay Disarmed
The relay at this address has been dis-
armed from the Control menu.
Relay Driver Inoperative
The relay on the CRM-4 or CSM-4 at this
address does not operate when com-
manded to energize.
Relay Supervision Failure
The relay at this address has a coil failure.
ROM SW Version Error
Module at the address noted needs an
update to latest available software level.
Signal Circuit Disarmed
The NAC at this address was disarmed
from the Control panel.
Signal Circuit Loop Open
The NAC at this address has a broken wire
or missing EOL device.
Signal Ckt Loop Shorted
The NAC at this address is shorted, or the
EOL device is the wrong value, or the
notification appliances are not polarized or
are connected backwards.
PRE 2 Level
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...