3-2
Operation
System Modules
ALD-2I Analog Loop Module
The ALD-2I takes two adjoining module
addresses. Loop 1 of the ALD-2I is at any
module address and loop 2 at the next
address. The analog loops on the SMB-2
are at module addresses 1 and 2 (See
Table 17, page 3-1) and cannot be moved.
The table below illustrates ALD-2I module
addresses:
ALD at Module
Addresses 3 and 4
Devices
Loop 1
003-001 to 003-060
Loop 2
004-001 to 004-060
ALD at Module
Addresses 15 and 16 Devices
Loop 1
015-001 to 015-060
Loop 2
016-001 to 016-060
CSM-4 Signal Module
The CSM-4 module contains two circuits
and two programmable LEDs.
Their device addresses on the module are
as follows:
Circuit 1
001
Circuit 2
002
LED 1
005
LED 2
006
For example, the address of circuit 2 on the
CSM-4 at module address 3 is 003-002.
CRM-4 Relay Module
The CRM-4 Relay module contains four
relays and two controllable LEDs.
Their device addresses on the module are
as follows:
Relay 1
001
Relay 2
002
Relay 3
003
Relay 4
004
LED 1
005
LED 2
006
For example, the address of relay 4 on the
CRM-4 at module address 20 is 020-004.
CZM-4 Conventional Zone Module
The CZM-4 Conventional Zone module
contains four conventional initiating device
zones and two programmable LEDs. Their
device addresses on the module are as
follows:
Zone 1
001
Zone 2
002
Zone 3
003
Zone 4
004
LED 1
005
LED 2
006
For example, the address of zone 1 on the
CZM-4, at module address 105, is 105-001.
MKB Keyboard/Annunciator
The MKB Keyboard/Annunciator occupies
the fixed module address 251 (See Table
17, page 3-1).
SMB-2 Main Board
The SMB-2 occupies module addresses 1,
2, and 253. The module addresses 1 and 2
are analog loops.
Module address 253 contains two notifica-
tion appliance circuits (NACs) and two
relays. The device addresses at module
253 are as follows:
Common alarm relay
001
Common trouble relay
002
NAC 1
004
NAC 2
005
For example, the address of the common
alarm relay at module address 253 is
253-001.
Remote System Modules
MOI-7 Voice and Annunciator Driver
The MOI-7 occupies one network address
and one network node in the MXL-IQ
System. Set the address on S1 (See Figure
17, page 1-10) according to Table 16, page
2-19, so that it agrees with the address
assigned in CSG-M.
The MOI-7 has a set of 128 subaddresses
reserved for the MOD-16 open collector
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...