3-23
Operation
Press ENTER to select LIST. The System
displays the first List menu, with the S in
STATUS blinking:
LIST: STATUS ALARM SUPERVSRY
(To end a menu session and return to the
Main Menu or to leave the menu at any
time, press the Up arrow key to go back-
ward one menu each time.)
List: Status
The List Status function shows you the
number of acknowledged and unacknowl-
edged alarms, supervisories, security
conditions, and troubles, in that order.
From the List menu, use the Right or Left
arrow keys to cause the S in STATUS to
blink.
(If you press HELP at this point, the System
explains the List Status function:
SHOW NUMBER OF ACKED & UNACKED
Press HELP again to return to the List
menu.)
When you press ENTER to select List
Status, the display first shows the total
number of alarms and the number of
acknowledged alarms:
2 ALARM 2 ALARM ACK
To view, in order, the status of
supervisories, troubles, and security
conditions, press NEXT.
After the Security display, the System
returns to the List menu.
To make a printed list of current status,
press PRINT when the S in STATUS is
blinking. The System will print a listing
similar to the following:
System Status at 11:02:26 Jul 01, 20XX:
2 ALARM 2 ALARM ACK
0 SUPERV 0 SUPERV ACK
0 SECURITY 0 SECURITY ACK
30 TROUBLE 30 TROUBLE ACK
In the above printed message, there are two
alarms, both of them acknowledged, no
supervisory conditions, no security condi-
tions and 30 trouble conditions, all acknowl-
edged.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)
List: Alarm
The List Alarm function shows you all the
fire alarms currently in the System in the
order they occurred.
From the List menu, use the Left or Right
arrow key to cause the A in ALARM to
begin blinking.
If you press HELP at this point, the System
explains the List Alarm function:
SHOW INDIVIDUAL ALARM STATUS
Press HELP again to return to the List
menu.
Press ENTER to select ALARM and display
alarm information on the MKB-4 display.
If There Is No Fire Alarm:
If there is no fire alarm, the System briefly
displays the following message and then
returns you to the List menu:
NO ALARM EXISTS
If There Is a Fire Alarm:
If there is at least one fire alarm, the System
shows the most recent alarm, alternating
between the following two displays:
1-001
[custom message]
002
[device type]
IN ALR
1-001
[custom message]
002
[time/date]
IN ALR
Press NEXT to show the two displays for the
previous alarm in the sequence. (Pressing
HOLD freezes a display for as long as you
keep HOLD depressed.)
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...