3-9
Operation
Message 2:
1-001
[custom message]
002
[time/date]
IN SEC
Message 3:
ALARMS=000 SUPERVISORIES=000
SECURITIES=000
TROUBLES=002
In addition, the System responds to security
conditions with programmed output functions.
In the messages above, 1-001 represents
the address of the device reporting the
security condition.
002 in the first message tells you that this is
the second (and the most recent) of two
security conditions received.
The status information in the third message
reports the total number of alarms, super-
visories, troubles, and security conditions.
If your System includes a printer, it prints a
message from two to four lines long similar
to the following:
SECURITY IN 1-1 11:59:59 DEC 31, 20XX
#1
[custom message], [device type]
In the preceding printed message, SECU-
RITY indicates that the type of occurrence
is a security condition; 1-1 is the device
address; #1 is the number of the security
condition in the list of security conditions;
[custom message] is a custom message
entered using the CSG-M Custom Software
Generator (See the CSG-M Programming
Manual, P/N 315-090381); [device type] is
the type of device which reported the
security condition.
Viewing the List of Security Conditions
To see the security condition list when there
is more than one security condition, press
NEXT on the MKB-4 (the System displays
the most recent security condition first).
How to Individually Acknowledge a
Security Condition (UL 1076)
1. Press SEC ACK. The System
acknowledges the security condition
displayed and then displays the next
unacknowledged security condition.
How to Individually Acknowledge a
Supervisory (NFPA 72 Proprietary, UL 1076)
1. Press SUPV ACK. The System
acknowledges the supervisory displayed
and then displays the next
unacknowledged supervisory.
If your system has a printer, it prints an
acknowledgment message similar to the
following:
ACK SUPERV 1-5 12:01:28 DEC 3,20XX
#2
[custom message], [device type]
Note that the acknowledgment message
includes the term ACK to indicate this
supervisory was acknowledged.
2. Continue acknowledging supervisories
as explained above until the System
displays the following message: ALL
SUPERVISORIES ACKNOWLEDGED.
The SUPERVISORY LED glows steadily
to indicate that all supervisories are
acknowledged. If there are no troubles or
security conditions still in the System, the
internal audible goes silent; if any of
those conditions still exist, the internal
audible pulses.
3. If your System includes a printer, it prints
the following message:
ACK SUPERVISORY 12:05:44 DEC 3,20XX
ALL SUPERVISORIES ACKNOWLEDGED
Security
How The System Annunciates Security
Conditions
When a security condition is detected, the
System causes the SECURITY LED on the
MKB-4 to flash, the System’s internal
audible to sound, and the alphanumeric
display on the MKB-4 to alternate in a
sequence among the three messages
shown below. This example assumes that
two security conditions were received (See
the explanations below the messages).
Message 1:
1-001
[custom message]
002
[device type]
IN SEC
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...