3-32
Operation
Listing of Output States for Module 1 (ALD):
1-Auxiliary Output: OFF
2-Auxiliary Output: ON
3-Auxiliary Output: ON
4-Auxiliary Output: OFF
List: Device Usages
Use List Device Usages to show the uses
of individual devices as programmed in
CSG-M.
From the List menu, use the left or right
arrow key to cause the D in DEV_USAGES
to start blinking:
LIST: DEV USAGES
(If you press HELP at this point, the System
displays:
SHOW/PRINT DEVICE USAGES
Press HELP again to return to the List
menu.)
Display the Usage of One Device
Press ENTER to select List Dev_usages.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE: 001-001
Type the three-digit module number and
three-digit device number using the nu-
meric keypad and press ENTER. (Enter all
leading zeros.)
The System displays the use of the device
specified (i.e., Alarm, Trouble, or Status).
Press NEXT to display the address and use
of each succeeding device. When the
System has shown the uses of all devices
at that address, it returns to the List menu.
To leave the List Dev_usage menu without
going through all subaddresses, press the
Up arrow key. The System displays the List
menu.
Print the Device Usages of Devices Assigned
to a Specified Module
Press PRINT when the D in DEV_USAGES
is blinking. The System then asks for a
module number.
TYPE IN MODULE NUMBER: [module number]
Type the three-digit module number and
press ENTER. (Enter all leading zeros.)
The System prints the uses of all of the
devices assigned to that module.
Listing of Device Usages for module 1 (ALD)
1- ALARM 2- TROUBLE 3- STATUS
4- ALARM 5- TROUBLE 6- OUTPUT ONLY
List: Node Address
Use List Node Address to show the panel's
X-Net node address.
From the List menu, use the left or right
arrow key to cause the N in NODE AD-
DRESS to start blinking:
LIST: NODE ADDRESS
Display the Node Address
Press ENTER to select List Node Address.
The System displays the X-Net node
address for that particular MXL-IQ panel.
List: Air Sampling
Use List Air Sampling to display operational
characteristics of the Air Sampling devices.
Press ENTER when the A in AIR SAMPLING
is blinking to select List AIR SAMPLING.
Use the Left or Right arrow to move to the
following selections:
AIR SAMPLING: Smoke Lev Flow Lev
Trip Pts
(If you press HELP at this point, the System
displays:
DISPLAY AIR SAMPLING SMOKE LEVEL
Press HELP again to return to the List
menu.)
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...