1-16
Description
ILI-1B Intelligent/Analog Ionization Air-
Duct Detector
The ILI-1B is an intelligent/analog ionization
detector for use in air duct applications at
altitudes of 0 to 4000 feet. It uses either the
AD-3I housing or the AD-3XRI housing.
ILI-1BH Intelligent/Analog Ionization
Air-Duct High Altitude Detector
The ILI-1BH is an intelligent/analog ioniza-
tion detector for use in air duct applications
at altitudes of 3000 to 8000 feet. It uses
either the AD-3I housing or the AD-3XRI
housing.
ILP-1 Intelligent/Analog Photoelectric
Detector
The ILP-1 is an intelligent/analog photo-
electric detector that can be used as an
area or duct detector [ILP-1(d)]. It uses either
a DB-3S low profile mounting base, a
DB-X3RS mounting base with relay, an
AD-3ILP or AD-3XRILP duct housing, or an
ADBI-60 audible base.
ILPT-1 Intelligent/Analog Photoelectric
Detector with Heat Sensor
The ILPT-1 is an intelligent/analog rate-
compensated/fixed-temperature type
thermal and photoelectric detector. It can
only be used as an area detector. It uses
either a DB-3S low profile mounting base,
a DB-X3RS mounting base with relay, or
an ADBI-60 audible base.
ILP-2 Intelligent/Analog Photoelectric
Detector
The ILP-2 is an intelligent/analog photo-
electric detector that can be used as an
area or duct detector [ILP-2(d)]. It uses
either a DB-3S low profile mounting base,
a DB-X3RS mounting base with relay, an
AD-3ILP or AD-3XRILP duct housing, or an
ADBI-60 audible base. The ILP-2 requires
MXL-IQ Rev. 3.0 or higher firmware.
ILT-1 Intelligent Thermal Detector
The ILT-1 is an intelligent rate-compen-
sated/fixed-temperature type thermal
detector. It uses either a DB-3S low profile
mounting base, a DB-X3RS mounting base
with relay, or an ADBI-60 audible base.
LIM-1 Loop Isolator Module
The LIM-1 is a loop isolator module that
isolates short circuits on MXL-IQ analog
loops. The LIM-1 operates in both Class A
and Class B circuits.
MSI-10/20 Intelligent Manual Station
The MSI-10/20 is an intelligent manual
station designed to interface with an analog
loop. The MSI can be flush mounted or
surface mounted using the SB-5R mount-
ing box.
MSI-10B/20B Intelligent Manual Station
The MSI-10B/20B is an intelligent manual
station designed to interface with an analog
loop. The MSI-10B/20B can be flush
mounted or surface mounted using the
SB-5R mounting box.
MSI-B6F Intelligent Manual Station
The MSI-B6F is an intelligent manual station
designed to interface with an analog loop.
The MSI-B6F is a single-action station;
when used with the MS-FD adapter, the
MSI-B6F is a double-action station. The
MSI-B6F can be flush mounted or surface
mounted using the MS-FB backbox.
MSI-MB6 Intelligent Manual Station
The MSI-MB6 is an intelligent manual
station designed to interface with an analog
loop. The MSI-MB6 is a single-action
station; when used with the MS-DA plate,
the MSI-MB6 is a double-action station.
The MSI-MB6 can be flush mounted or
surface mounted using the MS-SB
backbox.
MS-MI Intelligent Manual Station
The MS-MI is an intelligent manual station
designed to interface with an analog loop.
The MS-MI is a single-action station; when
used with the MS-DA plate, the MS-MI is a
double-action station. The MS-MI can be
flush mounted or surface mounted using
the MS-SB backbox.
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...