1-10
Description
D2300CP Fiber Optic Interface
The D2300CP is a Fiber Optic interface for
the MXL’s RS-485 network, MNET or XNET.
It uses a two-fiber (Duplex) pair between
each device. The D2300CP can function as
either a repeater or an end point unit.
The D2300CP can operate in either a daisy
chain or star configuration. This allows for
network configurations that are not possible
with the RS-485 network alone.
WARNING:
The D2300CP module is not listed for use
by Factory Mutual. Applications requiring
fiber connectivity of voice modules/systems
are therefore not listed.
LLM-1 Leased Line Module
The LLM-1 provides telephone equipment
overvoltage suppression in compliance with
UL-864. The LLM-1 must be used with the
MXL System Modules CSM-4 and RCM-1.
MDACT Serial Dialer
The
MDACT is a multipoint serial dialer for
use in MXL systems where point identifica-
tion of alarm, supervisory, status or trouble
indication is required at central stations.
MID-16 Input Driver*
The MID-16 module provides 16 general
purpose inputs for user-defined operations
for the MXL-IQ.
The MID-16 is controlled by the MOI-7
module. Up to 8 MID-16s can be used with
an MOI-7. The function of each individual
input is defined by the use assigned to it in
CSG-M.
Figure 19
MID-16 Input Driver
Figure 17
D2300CP Fiber Optic Interface
Figure 18
MDACT Serial Dialer
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...