L-3
Appendix L
Fire Protection Company Name
CSG-M Memory=2900 used, 316874 free CONFIG => TWOSTG
Options, System Message, Authorizations
System Message -----------------> --- SIEMENS Building Technologies ---
Authorization Code-Level 1 -----> 11111
Authorization Code-Level 2 -----> 22222
Authorization Code-Level 3 -----> 33333
COUNTRY where installed --------> Canada
Language Selection -------------> ENGLISH and FRENCH
NFPA System Designation --------> NFPA A System
Backup Power Type --------------> 15 Amp Hour
Zone Coded Audible Format ------> TWO STAGE AUDIBLE - ZONE CODED/STEADY
Function Evaluation Limit ------> 32
Photo Detector Confirmation ----> 0
Ion Detector Confirmation ------> 0
Sys. Justified Alarm Time ------> 60
Intelligent Env. Compensation --> OFF
VDT Password Time Out (hh:mm) --> 00:05
Zone Coding Characteristics
Move Cursor to Highlight Selection, then ENTER ESC=Prev. Menu
Fire Protection Company Name
CSG-M Memory=2900 used, 316874 free CONFIG => TWOSTG
Zone Coding Characteristics
# rounds (3-15) ----------------> 5
Tempo --------------------------> 60/MIN
Final output status ------------> AUDIBLES ON
Inter-digit time (0.5-15 secs) -> 1.0
Inter-round time (0.5-15 secs) -> 2.0
Inter-group time (0.5-15 secs) -> 4.0
Minimum # round (3-15) ---------> 3
Zone Code Alarms After Silence -> YES
Move Cursor to Highlight Selection, then ENTER ESC=Prev. Menu
Selecting the Zone Coding Characteristics Menu
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...