3-46
Operation
Use the
NEXT
key to move through the
devices until you display the ones whose
LEDs you wish to test. Follow the instruc-
tions above.
When the System has displayed the
highest numbered device for the module
specified, it returns to the Test menu.
To turn on a device LED for a different
module, select
DEVICE_ LED
from the
Test menu and follow the preceding
instructions.
(To end a menu session and return to the
Main Menu, or to leave the menu at any
time, press the Up arrow key to go backward
one menu each time.)
Test: MOI Lamp Test
Use
MOI_lamp_test
to test the MOD-16
outputs of an MOI-7.
From the Test menu, use the Left or Right
arrow key to cause the
M
in
MOI
to start
blinking:
TEST: DEVICE LED MOI Lamp Test
(If you press
HELP
at this point, the System
displays:
TO TEST MOI-7 / MOD-16 LAMPS
Press
HELP
again to return to the above
menu.)
Press
ENTER
when the
M
is blinking to
select
MOI_LAMP_TEST
.
The System asks you to type the module
number. Type the three-digit module
number and press
ENTER
. (Enter all
leading zeros.)
If the MOI-7 module is present in CSG-M
the MOD-16 outputs will be placed in a 30-
second lamp test mode. After 30 seconds,
these outputs return to their previous state.
(To end a menu session and return to the
Main Menu, or to leave the menu at any
time, press the Up arrow key to go backward
one menu each time.)
Test: Network
(X-Network, M-Network)
This function is used only by Siemens
Industry, Inc., engineers to observe network
traffic so that they can evaluate the operation
of the module communication network.
Test: Override
Use
Test Override
to override the CSG-M
selected options for Alarm Verification and
Alarm Confirmation.
From the Test menu, use the Left or Right
arrow key to cause the
O
in
OVERRIDE
to
start blinking.
(If you press
HELP
at this point, the System
displays:
OVERRIDE ALARM VERIFY & CONFIRM
Press
HELP
again to return to the above
menu.)
Press
ENTER
when the
O
in
OVERRIDE
is
blinking and the menu displays:
OVERRIDE: ALR VERIFY ALR CONFIRM
Use the Left or Right arrow key to switch
between
ALR_VERIFY
and
ALR_CONFIRM
.
Override the Alarm Verification CSG-M
Selection
From the Override menu, press
ENTER
when the
A
in
ALR_VERIFY
is blinking to
select Alarm Verification.
The System shows the following menu:
OVERRIDE: YES NO
A blinking
Y
in
YES
indicates that Alarm
Verification Override is currently enabled. A
blinking
N
in
NO
indicates that the Alarm
Verification Override is currently disabled.
To enable Alarm Verification Override, use
the Left or Right arrow key to cause the
Y
in
YES
to start blinking. Pressing
ENTER
when the
Y
in
YES
is blinking will cause
Alarm Verification Override to be enabled.
Summary of Contents for MXL-IQ
Page 50: ...2 20 Installation ...
Page 126: ...A 2 Appendix A ...
Page 128: ...B 2 Appendix B ...
Page 138: ...F 4 Appendix F ...
Page 140: ...G 2 Appendix G ...
Page 142: ...H 2 Appendix H ...
Page 154: ...K 2 Appendix K ...
Page 162: ...L 8 Appendix L ...
Page 166: ...M 4 Appendix M ...
Page 168: ...N 2 Appendix N ...
Page 178: ...Index 6 Index ...