Motorized Two-Way Ball Valve 
with Screwed-End Connection 

 

General 

Model VY6300A/VY6300B is a series of motorized two 
way ball valve with screwed-end connection.   

Models VY6300A and VY6300B provide two-position con-
trol of chilled/hot water. 

The ball valves with little pressure loss are suitable for 
open/close operation. 

 

Features 

 Actuator (electrically motorized) provides smooth 

open/close operation so that water hammer is prevented 
when the valve is closed. 

  Valve is manually opened and closed by simply moving 

the lever or using the a wrench. 

 Output signal (voltage contact) for pilot lamp allows 

remote monitoring of Model VY6300. 

  Valve position is easily visible by checking the positon 

indicator located on the bottom or the bilateral sides of 
the actuator. 

 

  Dust-proof and splash-proof enclosure complies with IEC IP54. 

(IEC: International Electrotechnical Commission) 

 

Model Numbers 

Base 

model 

No. 

Actuator/Valve Actuator  Valve 

 

Description 

Control 

signal 

Rating/ 

Material 

Power 

 

Nominal 

size/Cv 

VY63 

 

 

 

 

 

Motorized two-way ball valve with screwed connection 

 0        

SPST 

  0     

2 MPa / Bronze casting (JIS CAC406) 
(JIS: Japanese Industrial Standards) 

 

 

 

 

 

100 V AC 

 

 

 

 

 

200 V AC 

    00   

 

 

 

 

 

 

11 

DN15 / 13 in Cv value 

 

 

 

 

 

21 

DN20 / 33 in Cv value 

 

 

 

 

 

22 

DN25 / 56 in Cv value 

 

 

 

 

 

31 

DN32 / 86 in Cv value 

 

 

 

 

 

41 

DN40 / 130 in Cv value 

 

 

 

 

 

51 

DN50 / 130 in Cv value 

 

Specifications/Instructions

Summary of Contents for VY63 Series

Page 1: ...gnal voltage contact for pilot lamp allows remote monitoring of Model VY6300 Valve position is easily visible by checking the positon indicator located on the bottom or the bilateral sides of the actuator Dust proof and splash proof enclosure complies with IEC IP54 IEC International Electrotechnical Commission Model Numbers Base model No Actuator Valve Actuator Valve Description Control signal Rat...

Page 2: ...mbly is prohibited Instructs users to carry out a specific obligatory action to prevent possible danger The symbol inside graphically indicates the actual action to be carried out For example the sign on the left indicates general in structions WARNING Before wiring or maintenance be sure to turn off the power to this product Failure to do might cause electric shock or device failure Be sure to gr...

Page 3: ... as a circuit breaker for the power to this product Provide a circuit protector e g a fuse cut off device for the control panel to ensure your safety Use crimp terminals with insulation for connections to the product terminals Failure to do so might cause short circuit leading to fire or device failure Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause fi...

Page 4: ...FE polytetrafluoroethylene O ring NBR nitrile butadiene rubber Actuator Actuator for DN15 to DN25 Case PC polycarbonate resin Cover PC polycarbonate resin Yoke PPS polyphenylene sulfide resin Actuator for DN32 to DN50 Case Aluminium die cast Cover PC resin Yoke SPCC cold rolled steel plate Allowable fluid temperature 5 C to 80 C Do not allow the fluid to freeze Allowable operating pressure Max 2 0...

Page 5: ... 33 30 5 Rc 3 4 1 3 25 92 46 120 51 5 149 5 58 5 78 41 29 5 Rc 1 1 6 Figure 2 Dimensions of Models VY6300X0031 VY6300X0041 VY6300X0051 mm Nominal size DN L mm L1 mm La mm La1 mm H mm H1 mm B mm D mm h mm Pipe thread Weight kg 32 106 53 140 70 212 5 74 5 165 50 40 Rc 11 4 3 6 40 122 61 140 70 218 5 80 5 165 56 40 5 Rc 11 2 4 4 50 142 71 140 70 218 5 80 5 165 69 40 5 Rc 2 4 9 Note Pipe thread compli...

Page 6: ...ion position Model VY6300 can be mounted onto vertical pipes as well as to horizontal pipes Model VY6300 can be mounted in any position from upright to sideways The valve should be installed with its actuator vertically positioned above the valve When Model VY6300 is installed outdoors it must be installed in upright position Figure 5 Valve and actuator mounting position Piping 1 When connecting t...

Page 7: ...ain unit and the indicator manual lever especially on the area with attached Be sure to disconnect the power supply before manually opening closing the valve DN15 DN20 or DN25 size Adjust the indicator manual lever with the lever release but ton as shown in Fig 10 pushed in Do not use any tool to adjust the indicator manual lever Figure 10 Manual open close operation for Model VY6300X0011 VY6300X0...

Page 8: ...Move the indicator manual lever to O with the lever release button pushed in 2 Move the lock lever to the right end Mount the actuator onto the valve 4 mounting positions are available To combine with the valve the actuator can be horizontally turned every 90 degrees based on the factory preset position 3 Make sure that the arrow on the top of the valve stem points at O and that the hole on the si...

Page 9: ...e hole on the side of the valve stem faces the direction to which the raised part of the mounting flange points Step 1 3 Remove the screws connecting the yoke and the valve body Step 2 4 Change the direction of the yoke to the desired direction The actuator and the yoke can be horizontally rotated every 90 degrees to fit into the valve mounting position 0 90 180 270 from the factory preset positio...

Page 10: ... the cover is always closed except during wiring work Wiring must be performed by qualified per sonnel in accordance with all applicable safety standards Never apply 100 V AC 200 V AC voltage to the terminal 4 ground terminal Be sure to remove all the metal chips made by cutting out a knockout hole inside the actuator For splash proof enclosure Be sure to completely close the terminal cover and th...

Page 11: ...e actuator cut out a knockout hole for a wiring port There are two knockout holes on the bilateral sides of the actuator terminal block one 22 mm knockout hole on each side Select a knockout hole according to the mounting direction of wiring couduit and cut out the knockout hole by lightly knocking it with a screwdriver See Fig 14 Figure 14 Knockout hole for wiring port 2 To connect the wires to t...

Page 12: ...ibration Valve hunting Fluid leakage to the outside Table 4 Troubleshooting Problem Part to check Action Valve does not operate smoothly valve stops halfway valve does not operate at all Conditions of the power applied and of the input signal applied Wiring condition disconnected wires Jammed foreign substance may block the valve open close operation Check the power supply and the controller conne...