Heat Insulation
Do not apply heat insulation to the actuator or to the yoke.
Apply heat insulation only to the area boxed with dotted lines
shown in Fig. 7 if necessary.
Figure 7. Heat insulation
Actuator
Model VY6300 features a single unit construction with the
actuator and valve combined together. Do not separate to
combine with another valve/actuator.
Position for shipment
The actuator shaft is positioned at ‘O’ (in fully open position)
for shipment. (See Figs. 8 and 9.)
Figure 8. Fully open position
of Model VY6300X0011/VY6300X0021/VY6300X0022
Figure 9. Fully open position
of Model VY6300X0031/VY6300X0041/6300X0051
Manually Opening/Closing the Valve:
Model VY6300X0011/VY6300X0021/VY6300X0022
CAUTION
To manually open or close the valve, be sure
to disconnect from the power supply
(100 V AC/200 V AC). If the valve is manually
opened or closed with the power applied, the
actuator may be damaged.
To prevent your finger from being pinched
and injured, do not put your fingers between
the main unit and the indicator/manual lever,
especially on the area with
attached.
Be sure to disconnect the power supply before manually
opening/closing the valve (DN15, DN20, or DN25 size).
Adjust the indicator/manual lever with the lever release but-
ton (as shown in Fig. 10) pushed in. Do not use any tool to
adjust the indicator/manual lever.
Figure 10. Manual open/close operation
for Model VY6300X0011/VY6300X0021/VY6300X0022
Model VY6300X0011/VY6300X0021/VY6300X0022
CAUTION
To manually open or close the valve, be sure
to disconnect from the power supply (100 V
AC/200 V AC). If the valve is manually
opened or closed with the power applied, the
actuator may be damaged
Never rotate the joint out of “0” to “100” range
of the scale.
Be sure to disconnect the power supply before manually
opening/closing the valve (DN32, DN40, or DN50 size). As
shown in Fig. 11, hold the joint with a tool such as a hexag-
onal wrench, and turn the joint slowly toward the position to
set up.
Figure 11. Manual open/close operation
for Model VY6300X0031/VY6300X0041/6300X0051
Indicator/manual lever
S
O
Indicator
Indicator/
manual lever
Gear release
button
Lock lever
(Do not release.)
Joint
Rotate.
DN15 to DN25 valves
DN32 to DN50 valves