Wiring
Wiring precautions
For 0.75 mm
2
or larger multiconductor cable, use a seal
connector (cable gland) requiring separate order. (Refer to
Table 2.) For 1.25 mm
2
or larger insulated wires, use the
conduit set (Part No. 83157240-004).
If Model VY6300 is used outdoors, be sure to waterproof the
cable (with conduits, flexible tubes, or water-proof plica
tubes) and the wiring port (with a seal connector).
Fig. 12 shows an example of the internal and external wiring
connections.
Figure 12. Internal and external wiring connections
CAUTION
Always disconnect the power source and
product power supply before performing any
wiring to prevent electrical shock or equip-
ment damage.
Do not apply any voltage other than the
specified (100 V AC/200 V AC). Motor and
printed circuit board (PCB) may burn out.
Make sure that the cover is always closed
except during wiring work.
Wiring must be performed by qualified per-
sonnel in accordance with all applicable
safety standards.
Never apply 100 V AC/200 V AC voltage to
the terminal 4 (ground terminal).
Be sure to remove all the metal chips, made
by cutting out a knockout hole, inside the
actuator.
For splash-proof enclosure...
Be sure to completely close the terminal cover and the top
cover.
Waterproof the wiring port.
Provide a seal connector (cable gland) specified in the
following (Table 2) with the wiring port .
Table 2. Part numbers of the water-proof connectors
Cable outer
diameter (mm)
Seal connector part numbers
DN15-DN25 valves
(Without lock nut)
DN32-DN50 valves
(With lock nut)
6 to
8
83104346-012 83104346-002
7 to
9
83104346-013 83104346-003
9 to
11
83104346-014 83104346-004
11 to
13
83104346-015 83104346-005
13 to
14.5
83104098-004 (without lock nut)*
Note: Be sure to separately provide a lock nut.
Waterproof the conduit.
Provide a water-proof plica tube or the like as a conduit.