Connecting
5.4 Electrical connection
FIDAMAT 6
46
Operating Instructions, 01/2019, A5E00222135-04
If the exhaust gas is to flow off into a collection line, observe the following points:
●
Keep the flow resistance in the collection line as low as possible by using a short line or
by using a transition to a larger diameter.
●
The exhaust gas line must be free of rapid pressure fluctuations. In case of pressure
fluctuations, take the following remedial actions:
–
Install a separate exhaust line.
–
Alternatively: Install a damping vessel (> 1 l) with a downstream restrictor between the
device and the exhaust line (pneumatic low pass).
●
Route the line with a constant downward gradient to prevent congestion in the exhaust
gas line (e.g. due to water condensation) and therefore damage to the device due to
water formation. We recommend connection of a siphon as a water separator. The
exhaust gas line connected to the device must have an inside diameter of at least 8 mm
due to condensate formation.
5.4
Electrical connection
5.4.1
Notes for electrical connections
Note
Improvement of interference immunity
•
Lay signal cables separately from cables with voltages > 60 V.
•
Use cables with twisted wires.
•
Install the device and lay its cables at a distance to strong electromagnetic fields.
•
Use shielded lines to guarantee the full specification according to Ethernet/PROFIBUS.
Note
Securing plug-in connections
Plug-in connections without interlock can loosen and fall out.
•
Secure plug-in connections without interlock mechanically, for example, with a cable tie.
Summary of Contents for FIDAMAT 6
Page 1: ...FIDAMAT 6 ...
Page 2: ......
Page 10: ...Table of contents FIDAMAT 6 8 Operating Instructions 01 2019 A5E00222135 04 ...
Page 38: ...Description 3 6 Communication FIDAMAT 6 36 Operating Instructions 01 2019 A5E00222135 04 ...
Page 76: ...Operation 7 6 Calibration FIDAMAT 6 74 Operating Instructions 01 2019 A5E00222135 04 ...
Page 134: ...Functions 8 6 Configuration FIDAMAT 6 132 Operating Instructions 01 2019 A5E00222135 04 ...
Page 176: ...Dimensional drawings FIDAMAT 6 174 Operating Instructions 01 2019 A5E00222135 04 ...
Page 186: ......
Page 198: ...Glossary FIDAMAT 6 196 Operating Instructions 01 2019 A5E00222135 04 ...
Page 201: ......
Page 202: ......