Chapter 3) 7SR158 Performance Specification
Chapter 3 - Page 14 of 24 ©2013 Siemens Protection Devices Limited
1.4.3.2
High Frequency Disturbance
IEC 60255-22-1
Type
Level
Variation
Case, Aux Power & I/O common (longitudinal) mode 2.5 kV
10 %
Case, Aux Power & I/O Series (transverse) mode
1.0 kV
RS485 Metallic Comms
1.0kV
No data loss
1.4.3.3
Electrostatic Discharge
IEC 60255-22-2 Class IV
Type
Level
Variation
Contact discharge
8.0 kV
5 %
1.4.3.4
Radiated Immunity
IEC 60255-22-3 Class III
Type
Level
Variation
80 MHz to 1000 MHz Sweep
10 V/m
5 %
1.4GHz to 2.7GHz Sweep
80,160,380,450,900,1850,2150 MHz Spot
1.4.3.5
Electrical Fast Transient / Burst Immunity
IEC 60255-22-4 Class A (2002)
Type
Level
Variation
Case, Aux Power & I/O
4.0 kV
10 %
RS485 Metallic Comms
2.0 kV
No data loss
1.4.3.6
Surge Immunity
IEC 60255-22-5, IEC 61000-4-5
Type
Level
Variation
Analog Inputs Line to Earth
4.0 kV
10 %
Case, Aux Power & I/O Line to Earth
2.0 kV
Analog Inputs Line to Line
1.0 kV
Case, Aux Power & I/O Line to Line
1.0 kV*
RS485 Comms port Line to Earth
1.0 kV
No data loss
* Note 45ms pick up delay applied to binary inputs
1.4.3.7
Conducted Radio Frequency Interference
IEC 60255-22-6
Type
Level
0.15 to 80 MHz
10 V