Chapter 4) 7SR158 - Data Communications
© 2013 Siemens Protection Devices Limited
Chapter 4 - Page 51 of 66
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
or 2 (Binary Output with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
or 2 (Binary Output Event with Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
or 2 (Command Status with Time)
FW#
Point
Index
Name
(Description)
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 10
Default
Variation
Event
Object 11
Default
Command
Event
Object 13
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Command
Event
Object 13
CROB
Supported
Operations
Default
CROB
Operations
Latch On
Latch Off
Close
Trip
113 User DP Command 7.
0
2
2
0
1
Pulse On
Pulse Off
Latch On
Latch Off
Close
Trip
Pulse On
Pulse Off
114 User DP Command 8.
0
2
2
0
1
Pulse On
Pulse Off
Latch On
Latch Off
Close
Trip
Pulse On
Pulse Off
5.3.4 Counters
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function
is performed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point.
The default Binary Counter and Frozen Counter event buffer sizes are set to 30.
The “Default Deadband,” and the “Default Change Event Assigned Class” columns are used to represent the
absolute amount by which the point must change before a Counter change event will be generated, and once
generated in which class poll (1, 2, 3, or none) will the change event be reported.
The default counter event buffer size is set 30. The counter event mode is set to Most Recent, only most recent
event for each point is stored.
Counters are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.