Chapter 4) 7SR158 - Data Communications
Chapter 4 - Page 46 of 66
© 2013 Siemens Protection Devices Limited
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
FW#
Point
Index
Name
(Description)
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
876 Unexpected Restart
0,2
2
2
877 Reset Start Count
0,2
2
2
900 User SP Command 1
0,2
2
2
901 User SP Command 2
0,2
2
2
902 User SP Command 3
0,2
2
2
903 User SP Command 4
0,2
2
2
904 User SP Command 5
0,2
2
2
905 User SP Command 6
0,2
2
2
906 User SP Command 7
0,2
2
2
907 User SP Command 8
0,2
2
2
972 78-1
0,2
2
2
973 78-2
0,2
2
2
974 81R-1
0,2
2
2
975 81R-2
0,2
2
2
976 81R-3
0,2
2
2
977 81R-4
0,2
2
2
978 81R-5
0,2
2
2
979 81R-6
0,2
2
2
5.3.2 Double Bit Input Points
The default double bit input event buffer size is set to allow 100 events.
Double bit inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Double Bit Input Points
Static (Steady-State) Object Number: 3
Change Event Object Number: 4
Static Variation reported when variation 0 requested: 1 (Double Bit Input w/o status)
or 2 (Double Bit Input with status)
Change Event Variation reported when variation 0 requested: 1 (Double Bit Input Change w/o Time)
or 2 (Double Bit Input Change with Absolute Time)
or 3 (Double Bit Input Change with Relative Time)
FW#
Point
Index
Name
(Description)
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 3
Default Variation
Event Object 4
0 CB 1
0,2
1
3
10 User DP Command 1
0,2
1
3
11 User DP Command 2
0,2
1
3
12 User DP Command 3
0,2
1
3