3.3
Voltage Protection: Neutral Overvoltage (59N)
Two Neutral Overvoltage (or Neutral Voltage Displacement) elements are provided
59NIT & 59NDT
.
The relay measures fundamental frequency residual voltage for this function. The relay can be connected to
directly measure residual voltage (3V0 input) i.e. ‘CT/VT CONFIG > Phase Voltage Config’ setting =
‘Vab,Vbc,3Vo’. Alternatively the value of residual voltage can be derived from the phase-neutral voltages i.e.
‘CT/VT CONFIG > Phase Voltage Config’ setting = ‘Van,Vbn,Vcn’.
The 59NIT element can be configured to be either definite time lag (DTL) or inverse definite minimum time
(IDMT),
59NIT Setting
sets the pick-up voltage level (3V0) for the element.
An inverse definite minimum time (IDMT) can be selected using
59NIT Char
. A time multiplier is applied to the
characteristic curves using the
59NIT Time Mult
setting (M):
ms
1
Vs
3Vo
M
*
1000
op
t
Alternatively, a definite time lag delay (DTL) can be chosen using
59NITChar
. When Delay (DTL) is selected the
time multiplier is not applied and the
59NIT Delay (DTL)
setting is used instead.
An instantaneous or definite time delayed reset can be applied using the
59NIT Reset
setting.
The 59NDT element has a DTL characteristic.
59NDT Setting
sets the pick-up voltage (3V0) and
59NDT Delay
the follower time delay.
Operation of the neutral overvoltage elements can be inhibited from:
Inhibit 59NIT
A binary or virtual input.
Inhibit59NDT
A binary or virtual input.
User Inhibit
Reylogic (graphical logic)
Figure 3-3 Logic Diagram: Neutral Overvoltage Element (59N)