![Siemens 7SR158 Argus Technical Manual Download Page 33](http://html.mh-extra.com/html/siemens/7sr158-argus/7sr158-argus_technical-manual_383099033.webp)
Chapter 1) 7SR158 Description of Operation
©2014 Siemens Protection Devices Limited Chapter 1) Page 29 of 38
4.2 Circuit Breaker
Both ‘CB Failed To Open’ and ‘CB Failed to Close’ features are provided.
CB Travel Alarm
The
CB Open
and
CB Closed
binary inputs are continually monitored to track the CB Status.
The CB should only ever be in 3 states:
CB Status
CB Open
binary input
CB Closed
binary input
CB is Open
1
0
CB is Closed
0
1
CB is Travelling between the above 2 states
0
0
The
CB Alarm
output is given where the Travelling condition exists for longer than the
CB Travel Alarm
setting.
An instantaneous
CB Alarm
is given for a 1/1 state – i.e. where the CB indicates it is both Open and Closed at
the same time.
CB Control Trip Time
When this is set to
Enabled
, the relay will measure the CB trip time following operation of either a CB control
open output or a CB Trip output. The trip time is displayed by the MAINTENANCE METERS > CB Trip Time
meter.
When this is set to
Disabled
, the relay will measure the trip time following operation of a CB Trip
output only. Operation of a CB control open output will then not cause the trip time to be measured.
Trip Time Alarm
The CB Trip Time meter displays the measured time between the trip being issued and the CB auxiliary contacts
changing state. If this measured time exceeds the
Trip Time Alarm
time, a
Trip Time Alarm
output is issued.
Trip Time Adjust
This allows for the internal delays caused by the relay – especially the delay before a binary input
operates – to be subtracted from the measured CB trip time. This gives a more accurate measurement
of the time it took for the CB to actually trip.
Open CB Pulse
The duration of the CB open pulse is user settable to allow a range of CB’s to be used. The
Open CB Pulse
must
be long enough for the CB to physically open.
Close CB Pulse
The duration of the
Close CB Pulse
is settable to allow a range of Circuit-Breakers (CB’s) to be used. The
Close
CB Pulse
must be long enough for the CB to physically close.
The Close pulse will be terminated if any protection pick-up operates or a trip occurs. This is to prevent Close and
Trip Command pulses existing simultaneously.
The output
CB Successful Close
confirms a successful CB Close operation.
The output
CB Fail to Close
is issued if the CB is not closed at the end of the close pulse,
Close CB Pulse
.
Summary of Contents for 7SR158 Argus
Page 1: ...Answers for energy 7SR158 Argus Voltage and Frequency Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR158 Argus Contents ...
Page 211: ......