Chapter 4) 7SR158 - Data Communications
© 2013 Siemens Protection Devices Limited
Chapter 4 - Page 9 of 66
2.3 RS485 Interface (COM1)
The 2-wire RS485 communication port is located on the rear of the relay and can be connected using a suitable
RS485 120 Ohm screened twisted pair cable.
The RS485 electrical connection can be used in a single or multi-drop configuration. The RS485 master must support
and use the Auto Device Enable (ADE) feature. The last device in the connection must be terminated correctly in
accordance with the master device driving the connection. This can be done via the internal 120 ohm terminating
resistor, which can be connected between 14 (A) and 18 (B) by fitting an external wire loop between terminals 18
and 20 on the power supply module.
The maximum number of relays that can be connected to the bus is 64.
The RS485 data comms link will be broken for that particular relay element if it is withdrawn from the case but the
chain of communication to the other relays is maintained.
The following settings, on the COMMUNICATIONS MENU, must be configured when using the RS485 interface.
Setting Name
Range/Options
Default
Setting
Notes
COM1-RS485
Protocol
OFF
IEC60870-5-103
MODBUS-RTU
DNP3
IEC60870-5-103
The protocol used
to communicate on
the standard RS485
connection.
COM1-RS485
Station
Address
0 - 254 for IEC60870-5-103
1 - 247 for Modbus RTU
0 - 65534 for DNP3.0
0
An address within
the range of the
relevant protocol
must be given to
identify the relay.
Each relay in a
network must have a
unique address.
COM1-RS485
Baud Rate
75 110 150 300
600 1200 2400 4800
9600 19200 38400
19200
The baud rate set
on all of the relays
connected to the
control system must
be the same as
the one set on the
master device.
COM1-RS485
Parity
NONE
ODD
EVEN
EVEN
The parity set on
all of the relays
connected to the
control system must
be the same and in
accordance with the
master device.
COM1-RS485
Mode
Local
Local or Remote
Remote
Remote
Refer to
, page
further explanation