Chapter 3) 7SR158 Performance Specification
©2013 Siemens Protection Devices Limited
Chapter 3 Page 19 of 24
2.3.5
Operate and Reset Level (59NIT)
Attribute
Value
V
op
Operate level
100 %
Vs
, 2 % or 0.5 V
Reset level
95 %
V
op
or 0.5 V
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
f
nom
± 5 %
5 %
2.3.6
Operate and Reset Time (59NIT)
Attribute
Value
t
basic
Starter operate time
65 ms, 20ms
3V
o
Applied Current (for Operate-Time)
DTL
10 x Vs
t
op
Operate
time
char = IDMTL
1
M
t
Vs
0
V
3
op
, 5 % or 65 ms
char = DTL
t
d
, 1 % or 40ms
Reset Time
char = IDMTL
t
res
, 5 % or 65ms
char = DTL
t
res
, 1 % or 40ms
Repeatability
1 % or 20ms
Overshoot time
< 40 ms
Disengaging time
< 100 ms
Summary of Contents for 7SR158 Argus
Page 1: ...Answers for energy 7SR158 Argus Voltage and Frequency Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR158 Argus Contents ...
Page 211: ......