Chapter 3) 7SR158 Performance Specification
Chapter 3 - Page 22 of 24 ©2013 Siemens Protection Devices Limited
2.6 81R Rate-of-Change-of-Frequency (df/dt)
2.6.1
Reference
Parameter
Value
R
s
Setting
0.050, 0.075 …10.0 Hz/s
t
d
Delay setting
0, 0.01 … 20, 20.1 ... 100, 101 ... 1000, 1010 ... 10000,10100
... 100000, 101000 ... 864000s
F
nom
Nominal Frequency
50 Hz or 60 Hz
2.6.2
Operate Level
Attribute
Value
R
op
Operate Level
R
s
, 50 mHz/s (Fnom 3Hz)
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
2.6.3
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
(for ROCOF 1.3x setting)
Typically 215 ms
Maximum 300 ms
Element basic operate time
(for ROCOF 2x setting)
Typically 185 ms
Maximum 200 ms
t
op
Operate time following delay
t
basic
+
t
d
, 1 % or 10 ms
Repeatability
1 % or 10 ms