Chapter 3) 7SR158 Performance Specification
©2013 Siemens Protection Devices Limited
Chapter 3 Page 9 of 24
1.2.4.2 AC Performance
Attribute
Value
Maximum peak current for
operation
V
BI
= 19 V
1.5mA
Response time @115V
RMS
AC
< 16ms
Response time when programmed to energise an
output relay contact (i.e. includes output relay
operation)
< 26ms
For AC operation the BI pick-up delay should be set to 0ms and the drop-off delay to 25ms.
For AC operation wiring should be less than 10 metres in length.
Figure 1.2-1 Binary Input Configurations Providing Compliance with EATS 48-4 Classes ESI 1 and ESI 2