Chapter 3) 7SR158 Performance Specification
©2013 Siemens Protection Devices Limited
Chapter 3 Page 13 of 24
1.4.3
Immunity
1.4.3.1
Auxiliary Supply Variation
IEC 60255-11
Type of Phenomena
Test
Specifications
Duration
Declared Operation
Voltage Dips
(DC auxiliary supply)
0% RV
50ms
(Claimed)
Normal Operation
1
40% RV
200ms
Normal operation
1
except where Dip falls below
the relay minimum voltage then Relay Restart
2
70% RV
500ms
Normal operation
1
except where Dip falls below
the relay minimum voltage then Relay Restart
2
Voltage Dips
(AC auxiliary supply)
0% RV
2.5/3
cycles
@50/60Hz
(claimed)
Normal Operation
1
40% RV
10/12
cycles
@50/60Hz
Normal Operation
1
70% RV
25/30
cycles
@50/60Hz
Normal Operation
1
Voltage Interruptions
(DC auxiliary supply)
0% RV
5s
Relay Reset
2
Voltage Interruptions
(AC auxiliary supply)
0% RV
250/300
cycles
@50/60Hz
Relay Reset
2
Alternating
Component In DC
(Ripple)
(DC auxiliary supply)
15% max and min
RV
Continuous Normal
operation
1
Gradual Shut-down/
Start-up
(DC auxiliary supply)
Max & min RV to
0V
60s
Relay Reset
0V
5minutes
Relay
Off
0V to min & max
RV
60s
Relay Restart
2
Reversal of DC
Power Supply polarity
Max reversed RV
1minute
24-60 V Dc models:
No operation
80-250 V DC, 115 V AC models:
Normal Operation
1
Key:
RV = Residual Voltage Test Value. Two conditions: (a) range voltage low-20% and
(b) range voltage high +20%
1
No effect on relay performance
2
Restart with no mal-operation, loss of data or relay damage