7SR158 Technical Manual
Chapter 1) Page 32 of 38 ©2014 Siemens Protection Devices Limited
Section 5: Supervision Functions
5.1 VT Supervision
This is a simple feature that allows the Relay to detect and report a tripping of the MCB protecting the measuring
VT’s. Operation of the
MCB Failed
binary input is reported by the
VTS
binary output.
5.2
Trip/ Close Circuit Supervision (74TCS & 74CCS)
The relay provides three trip and three close circuit supervision elements, all elements are identical in operation
and independent from each other allowing 3 trip and 3 close circuits to be monitored.
One or more binary inputs can be mapped to
74TCS-n.
The inputs are connected into the trip circuit such that at
least one input is energised when the trip circuit wiring is intact. If all mapped inputs become de-energised, due to
a break in the trip circuit wiring or loss of supply an output is given.
The
74TCS-n Delay
setting prevents failure being incorrectly indicated during circuit breaker operation. This delay
should be greater than the operating time of the circuit breaker.
The use of one or two binary inputs mapped to the same Trip Circuit Supervision element (e.g. 74TCS-n) allows
the user to realise several alternative monitoring schemes.
Figure 4-2 Logic Diagram: Trip Circuit Supervision Feature (74TCS)
Figure 4-3 Logic Diagram: Close Circuit Supervision Feature (74CCS)