Chapter 4) 7SR158 - Data Communications
Chapter 4 - Page 40 of 66
© 2013 Siemens Protection Devices Limited
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
17, 27, 28 (index)
30
5
short floating point
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
6
long floating point
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
31
0
Frozen Analog Input
- Any Variation
31
1
32-Bit Frozen Analog Input
31
2
16-Bit Frozen Analog Input
31
3
32-Bit Frozen Analog Input
(with Time of freeze)
31
4
16-Bit Frozen Analog Input
(with Time of freeze)
31
5
32-Bit Frozen Analog Input
(without Flag)
31
6
16-Bit Frozen Analog Input
(without Flag)
32
0
Analog Change Event
- Any Variation)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
32
1
32Bit-Analog
Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
2
16Bit-Analog
Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
3
32Bit-Analog
Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
4 (default -
see note 1)
16Bit-Analog
Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
5
short floating point
Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
6
long floating point
Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
7
short floating point
Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
8
long floating point
Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
33
0
Frozen Analog Event
- Any Variation
33
1
32-Bit Frozen Analog Event
(without Time)
33
2
16-Bit Frozen Analog Event
(without Time)
33
3
32-Bit Frozen Analog Event
(with Time)
33
4
16-Bit Frozen Analog Event
Summary of Contents for 7SR158 Argus