![Siemens 7SR158 Argus Technical Manual Download Page 136](http://html.mh-extra.com/html/siemens/7sr158-argus/7sr158-argus_technical-manual_383099136.webp)
Chapter 4) 7SR158 - Data Communications
Chapter 4 - Page 54 of 66
© 2013 Siemens Protection Devices Limited
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
FW#
Point
Index
Name
(Description)
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
174 V Phase A Max
0,3
2
4
0.010
100.000
175 V Phase B Max
0,3
2
4
0.010
100.000
176 V Phase C Max
0,3
2
4
0.010
100.000
177 V Phase AB Max
0,3
2
4
0.010
100.000
178 V Phase BC Max
0,3
2
4
0.010
100.000
179 V Phase CA Max
0,3
2
4
0.010
100.000
192 Freq Last Trip
0,3
5
7
1.000
1.000
196 Frequency Max
0,3
2
4
100.000
1.000
5.4 Additional Settings
The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are
common to all ports using this protocol.
Setting Name
Range/Options
Default
Setting
Notes
Unsolicited
Mode
DISABLED, ENABLED
DISABLED
As Required
Setting is only visible
when any port
Protocol is set to
DNP3.
Destination
Address
0 - 65534
0
As Required
Setting is only
visible when DNP3
Unsolicited Events
set to Enabled.
DNP3
Application
Timeout
5, 6 ... 299, 300
10s
As Required
Setting is only visible
when any port
Protocol is set to
DNP3.
Summary of Contents for 7SR158 Argus
Page 1: ...Answers for energy 7SR158 Argus Voltage and Frequency Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR158 Argus Contents ...
Page 211: ......