10
10.1
MAG 8000 water meter
Note
Further information
For further information, see certificates. (
http://www.siemens.com/processinstrumentation/
)
Meter
MAG 8000 Standard
(7ME6810)
MAG 8000 CT
(7ME6820)
Accuracy
Standard calibration
± 0.4% of rate ± 2 mm/s
-
Extended calibration
± 0.2% of rate ± 2 mm/s
-
OIML R49:2013
-
Class 1 (DN50, DN350-DN600)
and
Class 2 (DN50-DN600)
MI-001
-
Q3/Q1=315 (DN50-DN300 hori‐
zontal),
Q3/Q1=200 (DN350-DN600 hori‐
zontal)
NMI M 10
± 2.5% (Q1 ≲ Q ≲ Q4)
-
Media conductivity
Clean water > 20 μs/cm
Temperature
Ambient
−20 to +60 °C
(−4 to +140 °F)
−20 to +55 °C
(−4 to +131 °F)
Media
0 to 70 °C
(32 to +158 °F)
0.1 to 50 °C
(32 to +122 °F)
Storage
−40 to +70 °C
(−22 to +158 °F)
−40 to +70 °C
(−22 to +158 °F)
Enclosure
IP68/NEMA 6P rating.
Cable glands mounted requires Sylgard potting kit to remain IP68/
NEMA 6P,
otherwise IP67/NEMA 4 rating is obtained.
Factory mounted cable provides IP68/NEMA 6P rating
Approvals
Drinking water approvals
NSF 61 (cold water) USA
WRAS (BS 6920 cold water) UK
ACS Listed France
DVGW W270 Germany
Belgaqua (B)
FM Fire Service (Class Number
1044)
NSF 61 (cold water) USA
WRAS (BS 6920 cold water) UK
ACS Listed France
DVGW W270 Germany
Belgaqua (B)
FM Fire Service (Class Number
1044)
KIWA
SITRANS FM MAG 8000
Operating Instructions, 03/2020, A5E03071515-AH
93
Summary of Contents for 7ME6810
Page 16: ...Description 3 4 Benefits SITRANS FM MAG 8000 16 Operating Instructions 03 2020 A5E03071515 AH ...
Page 140: ...Unit conversion table SITRANS FM MAG 8000 140 Operating Instructions 03 2020 A5E03071515 AH ...
Page 168: ...Features SITRANS FM MAG 8000 168 Operating Instructions 03 2020 A5E03071515 AH ...