Param‐
eter ID
Meter
version
Display
view
Parameter/data type
Factory settings
Data range
Fixed parameter or meter data that are not changeable
268
All
-
Low impedance fault appears 2000-01-01 T 00:00:00
269
All
-
Low impedance fault disap‐
pears
2000-01-01 T 00:00:00
270
All
-
High flow alarm output enable No
Yes / No
271
All
-
High flow alarm fault timer
0
272
All
-
High flow alarm fault counter
0
273
All
-
High flow alarm fault appears 2000-01-01 T 00:00:00
274
All
-
High flow alarm fault disap‐
pears
2000-01-01 T 00:00:00
275
All
-
Reverse high flow alarm out‐
put enable
No
Yes / No
276
All
-
Reverse high flow alarm fault
hours
0
277
All
-
Reverse high flow alarm fault
counter
0
278
All
-
Reverse high flow appears
2000-01-01 T 00:00:00
279
All
-
Reverse high flow disappears 2000-01-01 T 00:00:00
F.4
300-399
Param‐
eter ID
Meter
version
Display
view
Parameter/data type
Factory settings
Data range
Fixed parameter or meter data that are not changeable
300
All
-
Totalizer volume unit factor MLFB-dependent
0 to 1*x0
10
301
All
-
Flow unit factor
MLFB-dependent
0 to 1*x0
10
302
All
-
Pipe size
Sensor-related
25 to 1200
303
All
-
Meter excitation frequency
(in battery power mode)
1/15 Hz
1/60 Hz, 1/30 Hz, 1/15 Hz, 1/5 Hz,
1.5625 Hz, 3.125 Hz, 6.25 Hz
304
All
-
Mains frequency
MLFB-dependent
50 or 60 Hz mains
305
All
-
Decimal point
MLFB-dependent
No point, One digit after point, Two
digits after point, Three digits after
point, Automatic point adjust
306
All
-
Displayed unit
Use m
3
unit
Displayed m
3
unit or an arrow indica‐
tion for a unit label
307
All
-
Measurement direction
MLFB-dependent
Bidirectional, Forward only, Reverse
only
310
All
-
Flow direction totalizer 1
Forward
Forward, Reverse or Bi-directional
net flow
311
All
-
Totalizer 1 changes date
PS3 production date
and time
312
All
-
Flow direction totalizer 2
MLFB-dependent
Forward, Reverse or Bi-directional
net flow
Parameter lists
F.4 300-399
SITRANS FM MAG 8000
146
Operating Instructions, 03/2020, A5E03071515-AH
Summary of Contents for 7ME6810
Page 16: ...Description 3 4 Benefits SITRANS FM MAG 8000 16 Operating Instructions 03 2020 A5E03071515 AH ...
Page 140: ...Unit conversion table SITRANS FM MAG 8000 140 Operating Instructions 03 2020 A5E03071515 AH ...
Page 168: ...Features SITRANS FM MAG 8000 168 Operating Instructions 03 2020 A5E03071515 AH ...