Electrical installation
Tip
The function assigned to the "IN 4" input can be modified on the D
EVICE
C
ONFIGURATION
tab
in the CLV-Setup program.
¾
Click the F
UNCTION
I
N
4 drop-down list and choose the required function.
5.5.8
Connecting the "Result 1 ... Result 2" switching outputs
The four switching outputs can be assigned different functions for outputting result statuses
independently of each other. If the assigned event occurs during the reading procedure, the
corresponding switching output becomes live at the end of the reading pulse for the select-
ed pulse duration. The pulse duration can be set individually for each output.
The "Read Result" LED is linked to the "Result 2" output and lights up in Reading mode for
the selected pulse duration and function of the result status display (default: Good Read,
100 ms).
shows the connections for the "Result 1 ... Result 4" switching outputs.
shows the pin assignment on the CLX and the terminal assignment in the
AMV/S 60.
contains the characteristic data for these outputs. The
four outputs have the same characteristic data.
¾
Connect the outputs as shown in
.
Fig. 5-6:
Connections of the "Result 1 ... Result 4" switching outputs
V
S
= +18 ... +30 V DC for CLX without heater,
24 V DC +20 %/–10 % for CLX with heater
Pin and terminal assignment
for
Result X
Pulse duration
depending
on setting:
– 10 ms ... 900 ms
– 100 ms ... 9 900 ms
– 0 0 : static
(to the end of next
reading pulse)
GND
Result X
Fuse
Result X
Y
GND
R
L
V
S
5
Logic
Temperature
sensor
AMV 60-011/
AMS 60-012, -013
Terminal assignment
Z
T. 35
Output
Result X
CLX "I/O" connection
Pin Y
AMV/S 60
Terminal Z
Result 1
Pin 4
T. 31
Result 2
Pin 8
T. 32
Result 3
Pin 10
T. 33
Result 4
Pin 15
T. 34
Table 5-21: Pin and terminal assignment for "Result 1 ... Result 4" switching outputs