7
Service
Error list
Compact Operating Instructions – MOVIMOT
®
MM..D with AS-Interface
62
Code
Error
Possible cause
Measure
84
Thermal overload of
motor
Motor protection is active
when the MOVIMOT
®
in-
verter is mounted close to
the motor.
Set DIP switch S1/5 to "ON".
Reset error
1)
.
Incorrectly set performance
level when MOVIMOT
®
in-
verter and motor are com-
bined.
Check DIP switch setting S1/6.
Reset error
1)
.
Ambient temperature too
high.
Lower ambient temperature.
Reset error
1)
.
Heat build-up on
MOVIMOT
®
drive.
Prevent heat build-up.
Reset error
1)
.
Motor load too high.
Reduce the load on the motor.
Reset error
1)
.
Speed too low.
Increase speed.
Reset error
1)
.
Should the error occur
shortly after the initial ena-
ble.
Check the combination of motor and
MOVIMOT
®
inverter.
Reset error
1)
.
The temperature monitor-
ing in the motor (TH wind-
ing thermostat) has tripped
when using MOVIMOT
®
in-
verter with the selected ad-
ditional function 5.
Reduce the load on the motor.
Reset error
1)
.
89
Overtemperature in
brake
Thermal overload brake
coil
Extend the ramp time.
Reset error
1)
.
Brake coil defective.
Contact SEW Service.
Brake coil and braking re-
sistor connected.
Connect either brake or braking resistor on the
drive.
Inverter is not suitable for
the motor.
(only if the error occurs af-
ter the initial enable)
Check the combination of motor (brake coil)
and MOVIMOT
®
inverter.
Check/correct settings of DIP switch S1/6 and
S2/1.
Reset error
1)
.
90
Output stage detec-
tion
Assignment of inverter to
motor is not permitted.
Check/correct settings of DIP switch S1/6 and
S2/1.
Check/correct motor connection type.
Check whether the drive ID module is suitable
for the motor and is correctly connected.
Use MOVIMOT
®
inverter or motor with a differ-
ent power rating.
21328994/EN – 11/2014