Chapter 5 Configuring
T H E P M 1 3 0 P L U S
Configuring
M E T E R S E C U R I T Y
PM130 PLUS Powermeter Series
93
Daylight Saving Time
When the daylight saving time is enabled, the meter automatically
advances the device clock by one hour when daylight saving time begins
and puts the clock back one hour when it ends. The default daylight
saving time change points are preset for the U.S.A.
The daylight saving time option is disabled in the PM130 by default. If the
daylight saving time option is disabled, you need to manually adjust the
device clock for daylight saving time.
Time Synchronization Pulses
External time synchronization pulses can be delivered through one of the
digital inputs.
If a digital input is selected as the time synchronization source, the edge
of an external pulse adjusts the device clock at the nearest whole minute.
The time accuracy could be affected by the debounce time of the digital
input, and by the operation delay of the external relay.
5.3
Configuring Meter Security
This setup allows changing the user password and enabling or disabling
password protection.
The password in your meter is preset to 0 at the factory, and password
protection is disabled.
Using the Front Display
Select the AccS entry from the main menu. See Viewing and Changing
Setup Options in Chapter 3 for information on configuring parameters via
the front display.
To change the password:
1.
Select the
PASS
entry in the middle window with the
UP
and
DOWN
arrow buttons.
2.
Press the
SELECT
button to activate the lower window.
3.
Use the
UP
and
DOWN
arrow buttons to adjust the password.
4.
Press
ENTER
to confirm the new password.
The new password is effective for both the display and
communication ports.
To enable or disable password protection:
1.
Select
CtrL
in the middle window using the
UP
and
DOWN
arrow
buttons.
2.
Press the
SELECT
button to activate the lower window.
3.
Use the
UP
and
DOWN
arrow buttons to select the option.
4.
ON
enables password protection and
OFF
disables password
protection.
5.
Press
ENTER
to confirm your new setting, or
ESC
to discard
changes.
6.
Press
ESC
to exit the menu.
When password protection is enabled, you are not able to
change the device settings through the display or