Chapter 5 Configuring
T H E P M 1 3 0 P L U S
General
M E T E R S E T U P
PM130 PLUS Powermeter Series
77
Wiring Mode
Description
3LN3
4-wire Wye using 2 PTs (2½ element), line-to-neutral voltage
readings
3LL3
4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings
3BLN3
3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-neutral
voltage readings
3BLL3
3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-line
voltage readings
2LL1
3-wire/4-wire connection using the current from one phase (1 CT) and the L-L
voltage from the other two phases
In 4LN3, 3LN3 and 3BLN3 wiring modes, Min/Max volts, volt
demands and voltage harmonics represent line-to-neutral
voltages; otherwise, they will be line-to-line voltages.
Device Options
The Device Options setup allows changing user-configurable device
options or putting the meter into energy test mode.
Using the Front Display
Select
OPtS
from the main menu. See
in Chapter 3 for information on configuring parameters via the
front display.
Using PAS
Select
General Setup
from the
Meter Setup
menu, and then click on the
Device Options
tab.
Table 21 lists available device options.
Table 21: User-configurable Device Options
Display
Label
Parameter
Options
Default
Description
P.cAL
Power Calculation
Mode
rEAc = using reactive
power S=f(P, Q),
nAct = using non-active
power Q=f(S, P)
S=f(P, Q) The method used for calculating
reactive and apparent powers
below)
roLL
Energy Roll Value
E, EH
10.E4 = 10000 kWh
10.E5 = 100000 kWh
10.E6 = 1000000 kWh
10.E7 = 10000000 kWh
10.E8 = 100000000 kWh
10.E9 = 1000000000 kWh
10000000 The value at which energy
counters roll over to zero
Ph.En
Phase Energy
Calculation
E, EH
diS = Disabled
En = Enabled
Disabled
Enables phase energy
calculations
tESt
Energy Test Mode
E, EH
OFF = disabled
Ac.Ei = Wh pulses
rE.Ei = varh pulses
Disabled
Setting this option puts the
meter into the energy test mode
Chapter 3)