Chapter 5 Configuring
T H E P M 1 3 0 P L U S
General
M E T E R S E T U P
PM130 PLUS Powermeter Series
83
Display
Label
Parameter
Options
Default
Description
PuLS
Pulse width 20-1000 ms
100 ms
The actual pulse width is a multiple of the
1-cycle time rounded to the nearest bigger
value.
The pause time between pulses is equal to
the pulse width.
Src
Pulse source NONE
Ac.Ei = kWh IMP
Ac.EE = kWh EXP
rE.Ei = kvarh IMP
rE.EE = kvarh EXP
rE.Et = kvarh TOT
AP.Et = kVAh TOT
NONE
Links a pulse relay to the internal energy
pulse source. The relay must be set into
either pulse, or KYZ mode.
Unit
Pulse rate,
kWh/Pulse
0.1-1000.0
1.0
kWh/Pulse
Defines the pulse weight in kWh units per
pulse
Generating Energy Pulses through Relay Outputs
To generate energy pulses through a relay output:
1.
Set a relay to either pulse, or KYZ mode, and then select a polarity
(active pulse edge) for energy pulses and a pulse width.
2.
Select a source energy accumulator and the pulse rate for your
output.
3.
Send your new setup to the meter.
Configuring Analog Outputs
The meter can be ordered with two optional analog outputs with options
for 0-1mA, ±1mA, 0-20mA and 4-20mA current outputs.
Using the Front Display
Select Aout from the main menu. This menu entry appears only if the
optional analog output module is plugged into the meter.
Use the
UP
and
D
OWN arrow buttons to scroll to the required analog
output.
To select the analog output option:
1.
Press the
SELECT
button to activate the middle window.
2.
Use the
UP
and
DOWN
arrow buttons to scroll to the required
parameter.
To change the parameter value:
1.
Press the
SELECT
button to activate the lower window.
2.
Use the
UP
and
DOWN
arrow buttons to select the required value.
3.
Press
ENTER
to confirm the new parameter setting or press
ESC
to
discard changes.
4.
You are returned to the middle window and can configure other
parameters.
To store your new settings:
1.
Press the
ENTER
button when the middle window is highlighted.
2.
You are returned to the upper window and can select another analog
output or exit the menu.
3.
Press
ESC
to exit the menu.