Appendix A Technical Specifications
PM130 Powermeter Series
141
A.12
Measurement Specifications
Table 33: Measurement Specifications Parameters
Parameter
Full Scale @ Input
Range
Accuracy
Range
%
Reading
% FS
Conditions
Voltage
120VxPT @ 120V
400VxPT @ 690V
0.2
0.02
10% to 120% FS 0 to 1,150,000 V
Starting voltage
1.5-5.0% FS (selectable)
Line current
CT
0.2
0.02
For In = 5A
1% to 200% FS
For In = 1A
5% to 200% FS
0 to 50,000 A
Starting current 0.1% FS
Active power
0.36
PT
CT @ 120V
1.2
PT
CT @ 690V
0.3
0.02
|PF|
0.5
1
-10,000,000 kW to
+10,000,000 kW
Reactive power
0.36
PT
CT@ 120V
1.2
PT
CT @ 690V
0.3
0.04
|PF|
0.9
1
-10,000,000 kvar to
+10,000,000 kvar
Apparent power 0.36
PT
CT @ 120V
1.2
PT
CT @ 690V
0.3
0.02
|PF|
0.5
1
0 to 10,000,000 kVA
Power factor
1.000
0.2
|PF|
0.5,
I
2% FSI
-0.999 to +1.000
Frequency
50 Hz
60 Hz
25 Hz
400 Hz
0.02
0.04
V
L-N
> 25V
15 Hz to 70 Hz
15 Hz to 70 Hz
15 Hz to 70 Hz
320 Hz to 480 Hz
Total Harmonic
Distortion, THD
V (I), %Vf (%If)
999.9
1.5
0.2
THD
1%,
V
10% FSV and
V
L-N
> 25V,
I
10% FSI
0 to 999.9
Total Demand
Distortion, TDD,
%
100
1.5
TDD
1%,
I
10% FSI,
V
L-N
> 25V
0 to 100
Active energy
Import & Export
Class 0.5S under conditions as per
IEC 62053-22:2003
0 to 999,999,999 kWh
Reactive energy
Import & Export
Class 0.5S under conditions as per
IEC 62053-22:2003, |PF|
0.9
0 to 999,999,999 kvarh
Apparent energy
Class 0.5S under conditions as per
IEC 62053-22:2003
0 to 999,999,999 kVAh
PT - external potential transformer ratio
CT - primary current rating of the external current transformer
FSV - voltage full scale
FSI - current full scale
Vf - fundamental voltage
If - fundamental current
NOTES
1.
Accuracy is expressed as
(percentage of reading + percentage of full
scale)
1 digit. This does not include inaccuracies introduced by the user's
potential and current transformers. Accuracy calculated at 1second
average.
2.
Specifications assume: voltage and current waveforms with THD
5% for
kvar, kVA and PF, and reference operating temperature 20
C - 26
C.
1
@ 80% to 120% of voltage FS, 1% to 200% of current FS and frequency 50/60 Hz