Chapter 5 Configuring
T H E P M 1 3 0 P L U S
Configuring
C O M M U N I C A T I O N S
PM130 PLUS Powermeter Series
69
See Table 14
below for available communication options.
Table 14: COM Port Options
Display
Label
Parameter
Options
Default
Description
Prot
Protocol
ASCII = SATEC ASCII
rtu = Modbus RTU
dnP3 = DNP3
PrFb = Profibus DP (COM2)
Modbus RTU The communications
protocol for the port
Not changeable on COM2
with the Profibus module
rS
Interface
COM1: 485 = RS-485
COM2:
232 = RS-232
485 = RS-485
422 = RS-422
Eth = Ethernet
PrFb = Profibus DP
GPrS = GPRS modem
RS-485
Communication interface.
Not changeable on COM2
with the Ethernet and
Profibus modules
Addr
Device address SATEC ASCII: 0-99
Modbus: 1-247
DNP3: 0-65532
Profibus: 0-126
1
(126 for
Profibus)
Device network address
bAud
Baud rate
300 bps-115.2 kbps
9600 bps
The port baud rate
dAtA
Data format
7E, 8N, 8E
8N
Data format and parity.
7E data format should not
be used with the Modbus
RTU and DNP3 protocols
dLAY
Response delay 0-1000 ms
5 ms
The minimum time after
the last request character
is received to start the
transmission.
CPtb
ASCII
compatibility
mode
diS = Disabled
En = Enabled
Disabled
Enables a low-resolution
device emulation for
ASCII request “0” in high-
resolution devices (see
NOTES:
1.
The meter provides the permanent Modbus TCP server on port 502.
2.
Selecting the DNP3 protocol launches the second DNP3 TCP server in
addition to the Modbus server allowing simultaneous connections on
both ports. Selecting the Modbus protocol disables the DNP3 TCP
server.
3.
When you change the COM2 settings through the Ethernet port, the
device port restarts so communications will be temporarily lost. You
may need to wait some additional time until PAS restores a
connection with your device.
Setting Up Ethernet
Using the Front Display
Select
nEt
from the main menu.
This menu entry appears only if the
optional Ethernet module is plugged into the meter.
It allows you to
set up the meter network address and the default gateway.
Viewing and Changing Setup Options
in Chapter 3 for information on
configuring parameters via the front display.