SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
82/
148
4.3.4.3. Serial Communications Submenu
Menu
Submenu
Access level
Action
R001 – INVERTER MODBUS ADDRESS
Displays the Modbus address of the
inverter
A
Activates an alphanumeric keypad window.
Enter the desired value. The value will not take effect until you
restart the inverter.
R002 – RESPONSE DELAY
Displays the inverter response delay for
RS485 communications
A
Activates an alphanumeric keypad window.
Enter the desired value.
R003 – BAUD RATE
Displays the baudrate of RS485
communications
A
Activates a list window enabling selecting one of the following
items:
−
1200
−
2400
−
4800
−
9600
−
19200
−
38400
−
57600
R004 – TIME ADDED TO 4BYTETIME
Displays the time added to 4T byte-time on
RS485 port
A
Activates an alphanumeric keypad window.
Enter the desired value.
R005 – WATCHDOG SAFETY TIME
Displays the RS485 port watchdog safety
time
A
Activates an alphanumeric keypad window.
Enter the desired value.
R006 – PARITY BIT
Displays the parity bit setting of RS485
communications
A
Activates a list window enabling selecting one of the following
items:
−
DISABLE 1STOP
−
DISABLE 2STOP
−
EVEN
−
ODD
Table 13: Connectivity menu, Serial Communications submenu
R001
Range
1 ÷ 247
1 ÷ 247
Inverter Modbus
Address
Default
1
1
Level
ADVANCED
Address
588
Function
Determines the address of serial link 0, assigned to the inverter connected
to the network via RS485.
The value will not take effect until you restart the inverter. The reset
command may be run from the Commands submenu in the Tools menu.
R002
Range
1 ÷ 1000
1 ÷ 1000 ms
Response Delay
Default
5
5 ms
Level
ADVANCED
Address
589
Function
Determines the inverter response delay following a query sent by the
Master via the serial link.