INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 7500TL
99/
148
P087
Range
0 ÷ 32000
0 ÷ 320.000 s
Maximum
Voltage Reset
Time
Default
10 (Italy), 10 (Spain), 3000 (Germany)
Level
ADVANCED
Address
687
Function
This is the time during which the maximum voltage reset condition must be
maintained to prompt the reset of the grid maximum voltage fault.
P088
Range
60 ÷ 90
[60 ÷ 90] % of Vn
Minimum Voltage
Trip Threshold
Default
80 (Italy), 85 (Spain), 80 (Germany)
Level
ADVANCED
Address
688
Function
This parameter, expressed as a percentage of the rated grid voltage, sets
the activation threshold of the grid minimum voltage fault.
P089
Range
1000 ÷ 1200
1.000 ÷ 1.200
Minimum Voltage
Release Ratio
Default
1050
Level
ADVANCED
Address
689
Function
Sets the ratio between the trip threshold of the minimum voltage fault and
the value at which the minimum voltage fault is reset.
P090
Range
20 ÷ 1000
0.020 ÷ 1.000 s
Minimum Voltage
Trip Time
Default
50 (Italy), 150 (Spain), 150 (Germany)
Level
ADVANCED
Address
690
Function
This is the time during which the minimum voltage trip condition must be
maintained to prompt the activation of the minimum voltage fault.
P091
Range
0 ÷ 32000
0.0 ÷ 320.0 s
Minimum Voltage
Reset Time
Default
10 (Italy), 10 (Spain), 3000 (Germany)
Level
ADVANCED
Address
691
Function
This is the time during which the minimum voltage trip condition must be
maintained to prompt the grid minimum voltage fault reset.
P092
Range
50 ÷ 90
[50 ÷ 90] % of Vn
Instant Grid
Undervoltage
Threshold
Default
60
Level
ADVANCED
Address
692
Function
This parameter, expressed as a percentage of the grid rated voltage, sets
the activation threshold of the instant grid undervoltage fault.