SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
102/
148
Menu
GRID EVENTS
Submenu
Access
Level
Action
P108 – GRID OVERVOLTAGE EVENT
MASK
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter 0 or 1 to set the desired status.
P109 – GRID UNDERVOLTAGE EVENT
MASK
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter 0 or 1 to set the desired status.
P110 – GRID MINIMUM VOLTAGE EVENT
MASK
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter 0 or 1 to set the desired status.
P111 – GRID MAXIMUM VOLTAGE EVENT
MASK
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter 0 or 1 to set the desired status.
P112 – GRID RMS EVENT MASK
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter 0 or 1 to set the desired status.
P113 – FREQUENCY KO EVENT MASK
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter 0 or 1 to set the desired status.
Table 23: Tools menu, Advanced Configuration > Grid > Grid Events
P108
Range
0 ÷ 1
0: Inactive
1: Active
Grid Overvoltage
Event Mask
Default
1
1: Active
Level
ADVANCED
Address
708
Function
Sets the activation status of the grid overvoltage event.
P109
Range
0 ÷ 1
0: Inactive
1: Active
Grid
Undervoltage
Event Mask
Default
1
1: Active
Level
ADVANCED
Address
709
Function
Sets the activation status of the grid undervoltage event.
P110
Range
0 ÷ 1
0: Inactive
1: Active
Grid Minimum
Voltage Event
Mask
Default
1
1: Active
Level
ADVANCED
Address
710
Function
Sets the activation status of the grid minimum voltage event.